STEAM GENERATOR |
|
MANUFACTURER : Babcock & Wilcox. |
|
QUANTITY: Two (2) |
|
TYPE : Outdoors , drum type, pressurized unit. |
|
MCR FLOW : 286.8 Kg/s. |
|
100% FLOW : 259.5 Kg/s. |
|
SUPERHEATER OUTLET : 541 degrees C. |
|
REHEATER OUTLET : 541 degrees C. |
|
FUEL : Natural gas as primary fuel and info as backup fuel. |
|
|
|
MAIN TURBINE |
|
MANUFACTURER : Siemens. |
|
QUANTITY : Two (2). |
|
TYPE : Indoor single reheat , condensing with seven (7) uncontrolled extractions for feed water heating. |
|
THROTTLE CONDITIONS : 166.5 bard (abc), 537.8 degrees C,278.9 Kg/sec. |
|
|
|
MAIN GENERATOR |
|
QUANTITY : One (1) per unit. |
|
RATING : 320MW / 376.5 Mva, three phase, 20 Kv, 50 Hz, and 0.85 power factor lagging, 0.95 power factor
leading, SCR 0.52.
|
|
TYPE OF COOLING : Hydrogen cooled VWO 5% over pressure condition 347.6 MW. |
|
|
|
CONDENSER |
|
QUANTITY : One (1) per unit. |
|
RATING : Matched to turbine VWO , 5% over pressure conditions. |
|
EFFECTIVE COOLING SURFACE : 14.079 m square Tube Side Circulating. |
|
WATER FLOW RATE : 40.200 m 3/hr. |
|
COOLING WATER TEMPERATURE : 27 degrees Celsius. |
|
PRESSURE : 57.3 mm HgA. |
|
TUBES : Titanium. |
|
|
|
FEED WATER PUMPS |
|
QUANTITY : Two (2) 60% turbine - driven per unit, One (1). |
|
60% capacity constant speed motor- driven per unit |
|
TYPE : complete with tandem coupled booster pump. |
|
RATING : 112.200 lmp, 209 bar (abc). |
|
SUPPLIER : KSB. |
|
|
|
CIRCULATING WATER PUMPS |
|
QUANTITY : Two (2) , 50% motor- driven per unit. |
|
TYPE : Vertical. |
|
RATING : 20.100 m 3/hr, 18.5 m TDH (differential head). |
|
SUPPLIER : KSB. |
|
|
|
COMPRESSED AIR SYSTEM |
|
MAIN COMPRESSOR : three (3), 50% centrifugal type, oil free. |
|
CAPACITY : 2.102 Nm 3/hr. |
|
SUPPLIER : Ingersoll Rand. |
|
EMERGENCY COMPRESSOR : One (1), 35% (approx.) rotary type, oil free |
|
DRYERS : Two (2), 100% desiccant, heatless. |
|
RECEIVERS : Two (2). |